Three-phase 50 kW high-voltage hybrid inverter (IP66, 4 MPPTs, 200–800 V battery range, 100 A charge/discharge) for commercial self-consumption, peak shaving, and backup operation via the external GoodWe STS200-80-10 transfer switch. Pairs natively with GoodWe Lynx C (101–156 kWh) and BAT-AC (61.4 / 112.6 kWh) battery cabinets and holds VDE-AR-N 4105 and VDE-AR-N 4110 unit certificates.
- Rated AC output
- 50 kW
- Max PV input
- 75 kWp
- MPPT
- 4
- Battery voltage
- 200 – 800 V
- Matched batteries
- 5
GoodWe GW50K-ET-10

GoodWe ET 25–50 kW
Four MPPTs, one battery input
The PV-side 75,000 W ceiling and the separate STS condition belong to different design decisions.
Technical data
Battery
- Nominal battery voltage
- 500 V
- Battery voltage range
- 200 ~ 800 V
- Maximum charging power
- 55 kW
- Maximum discharging power
- 55 kW
- Maximum charge current
- 100 A
- Maximum discharge current
- 100 A
- BMS communication
- CAN
PV input
- Maximum PV input power
- 75000 WFootnote 1: For most PV modules, maximum PV input power can reach 2 × Pn (100 kW on GW50K-ET-10).
- Maximum input voltage
- 1000 V
- Nominal input voltage
- 620 V
- Start voltage
- 200 V
- MPPT voltage range
- 165 ~ 850 V
- MPPT voltage range at rated output
- 400 ~ 850 V
- Number of MPPTs
- 4
- Strings per MPPT
- 2
- Maximum input current per MPPT
- 42 / 32 / 42 / 32 A
- Maximum short-circuit current per MPPT
- 55 / 42 / 55 / 42 A
- PV standby voltage range
- 980 ~ 1000 VFootnote 3: Above 980 V the inverter enters standby mode and resumes normal operation once PV input voltage drops below 970 V.
AC output
- Rated active power
- 50 kW
- Maximum active power
- 50 kW
- Rated apparent power
- 50 kVA
- Maximum apparent power
- 50 kVA
- Maximum output current
- 75.8 @ 380V; 72.5 @ 400V A
- Grid connection
- 3L / N / PE
- Rated backup apparent power
- 50 kVARequires external GoodWe STS static transfer switch cabinet; max backup apparent power 55 kVA continuous (60 kVA for 60 s, 75 kVA for 10 s).
- Backup transfer time
- <20 msWith an external STS cabinet and a backup load below the inverter’s 50 kW rated power.
- Maximum efficiency
- 98.1 %
- European efficiency
- 97.5 %
- Battery-to-AC efficiency
- 97.7 %
Installation and operation
- Dimensions (W × H × D)
- 520 × 660 × 260 mm
- Weight
- 65 kg
- Ingress protection rating
- IP66
- Operating temperature
- -35 ~ +60 °C
- Maximum operating altitude
- 4000 m
- Topology
- Non-isolated
- Cooling
- Smart Fan Cooling
- Communication interfaces
- RS485, WiFi + LAN + Bluetooth, 4G + Bluetooth (Optional)
- Parallel operation
- Up to 10 units via SEC3000C
- Night-time power consumption
- <15 W
Project fit
Where this model fits.
Scenarios that show which projects the GoodWe GW50K-ET-10 belongs in, and the limits behind our engineers' recommendation.
Four tracker groups at the 50 kW step

Four PV input groups are being assigned to the 50 kW hybrid inverter.
The datasheet gives four MPPTs and one battery input; off-grid use requires an STS box.
- PV layout: allocate four MPPT groups.
- Off-grid use: add the STS box.
Documents

Product questions
Can a PV string on the GW50K-ET-10 operate continuously up to the 1,000 V maximum input voltage?
No. Footnote 3 on page 2 of the EMEA datasheet states that when the PV input voltage exceeds 980 V, the GW50K-ET-10 enters standby mode and returns to normal operation only after the PV voltage drops below 970 V. Its MPPT operating voltage range is 165–850 V (400–850 V at nominal power in the user manual, p. 72).
Which grid-connection certificates cover the GW50K-ET-10?
The GW50K-ET-10 holds both a low-voltage VDE-AR-N 4105:2018-11 unit certificate (TÜV Rheinland Registration No. A3 50626232 0001, report CN24WXK2 001, p. 3) and a medium-/high-voltage VDE-AR-N 4110:2023 and VDE-AR-N 4120:2018 unit certificate (Certificate No. 968/GI 2226.01/25, valid until 11 June 2030, PDF p. 1). The certification covers the inverter without the optional STS module (PDF p. 4).
Which battery cabinets work with the GW50K-ET-10?
GoodWe lists the Lynx C101-10, C120-10, C138-10 and C156-10 for the ET 40–50 kW. The battery BMS must be version 25600 or later (date in the serial number: 1 June 2024 or later; ET solutions manual, PDF p. 3). A single C101-10 or C120-10 cannot reach 50 kW. At nominal voltage the C138-10 and C156-10 have sufficient rated DC power; available power depends on operating voltage and current. The BAT-AC models GW61.4-BAT-AC-G10, GW102.4-BAT-AC-G10 and GW112.6-BAT-AC-G10 require inverter firmware ARM 10 or later.
Which accessories does the GW50K-ET-10 need for metering, parallel operation and backup?
For a single inverter, GoodWe supplies a GM330 or GM3000 meter and the meter cable. The GM330 needs separate current transformers (200–5,000 A primary, 5 A secondary). The GM3000 uses the transformers supplied with the meter. For up to ten inverters in parallel, GoodWe specifies the SEC3000C and one WiFi/LAN Kit-20 per inverter. All inverters must run the same software, with ARM 11.475 and DSP 4.400 or later. Backup uses the STS200-80-10 transfer cabinet with cabinet software 4.400 or later. With one inverter, GoodWe specifies transfer in under 10 ms for a backup load below 50 kW. If the inverters also operate in parallel off-grid, transfer takes under 20 ms and the total backup load must stay below 90% of their combined rating. If they operate separately off-grid, transfer takes under 10 ms and the load on each STS must stay below its inverter’s rated power (ET solutions manual, PDF pp. 30–32, 112, 115 and 117).
Which grid earthing systems and unbalanced phase loads does the GW50K-ET-10 support?
According to the user manual (pp. 10 and 24), the GW50K-ET-10 supports TN-S, TN-C, TN-C-S, and TT three-phase four-wire/five-wire grid configurations (380/400 V, 3L/N/PE) and unbalanced three-phase AC output up to 18.33 kW per phase.
What European manufacturer warranty applies to the GW50K-ET-10?
GoodWe’s European inverter warranty gives the GW50K-ET-10 five years of cover. The period starts at first installation or twelve months after production, whichever is earlier. If the installation date cannot be documented, GoodWe uses its shipment date in place of the installation date.
Compatibility records
| Compatible model | Category | Rating | Status & required accessory |
|---|---|---|---|
| GoodWe GW61.4-BAT-AC-G10Item number DLK-GOODWE-GW614BATACG10 | Battery Systems | 61.4 kWh | Released [1] [2] |
| GoodWe GW112.6-BAT-AC-G10Item number DLK-GOODWE-GW1126BATACG10 | Battery Systems | 112.6 kWh | Released [3] [2] |
| GoodWe LX C101-10Item number DLK-GOODWE-LXC10110 | Battery Systems | 101.38 kWh | Released [4] [5] [6] [7] |
| GoodWe LX C138-10Item number DLK-GOODWE-LXC13810 | Battery Systems | 138.24 kWh | Released [8] [6] [9] |
| GoodWe LX C156-10Item number DLK-GOODWE-LXC15610 | Battery Systems | 156.67 kWh | Released [10] [6] [9] |
- GoodWe's Battery Compatibility Overview (p. 6) lists GW61.4-BAT-AC-G10 for the ET (40–50 kW) series and requires inverter firmware ARM 10 or later. Battery charge/discharge power equals battery working voltage × min(battery current, 100 A).
- GoodWe's Battery Compatibility Overview (p. 6) requires ARM 10 or later on the ET (40–50 kW) series. For the BAT series it gives battery charge/discharge power as battery working voltage × the lower of battery charge/discharge current and 100 A, the maximum continuous charge/discharge current it states for the ET50.
- GoodWe's Battery Compatibility Overview (p. 6) lists GW112.6-BAT-AC-G10 for the ET (40–50 kW) series and requires inverter firmware ARM 10 or later. Battery charge/discharge power equals battery working voltage × min(battery current, 100 A).
- GoodWe's Battery Compatibility Overview (p. 6) lists LX C101-10 to LX C156-10 in its ET (40–50 kW) column; up to 3 identical Lynx C cabinets can be paralleled on one ET 40–50 kW battery input (Lynx C User Manual, p. 23).
- Footnote 2 on page 6 states that the ET 50 kW inverter with a single LX C101-10 (422.4 V nominal, 42.24 kW at 100 A) cannot reach the inverter's maximum 50 kW power.
- For use with ET 40–50 kW, the Lynx C cabinet requires BMS version 25600 or later (date in the serial number: 1 June 2024 or later). The stated DC power is at nominal voltage. Available power varies with battery temperature and state of charge.
- GoodWe's Battery Compatibility Overview (p. 6) lists LX C101-10 to LX C156-10 in its ET (40–50 kW) column. Its footnote states that the ET 50 kW with LX C101-10 or LX C120-10 cannot reach the inverter's maximum power.
- GoodWe's Battery Compatibility Overview (p. 6) lists LX C138-10 in its ET (40–50 kW) column; at 576.0 V nominal voltage and 100 A (57.60 kW), a single cabinet supports full 50 kW inverter output, and up to 3 identical cabinets can be paralleled (Lynx C User Manual, p. 23).
- GoodWe's Battery Compatibility Overview (p. 6) lists LX C101-10 to LX C156-10 in its ET (40–50 kW) column.
- GoodWe's Battery Compatibility Overview (p. 6) lists LX C156-10 in its ET (40–50 kW) column; at 652.8 V nominal voltage and 100 A (65.28 kW), a single cabinet supports full 50 kW inverter output, and up to 3 identical cabinets can be paralleled (Lynx C User Manual, p. 23).
Planning & Commissioning Guides
- System DesignHybrid Inverter vs. AC-Coupled Storage: A 4-Step Selection Guide for New Solar Builds and Retrofits
- Battery StorageEcoFlow, GoodWe, SAJ, and Pylontech: Four Diverging Storage Routes Reshaping Europe’s Solar Ecosystem (2026)
- Battery StorageHow to Size Battery Storage for Residential Backup: A 4-Step Guide to Critical Loads, Surge Power, Usable kWh, and Transfer Switches