Description
The GW99.99K-ET-G10 sits at a precise 99.99 kW nominal step, with 99.99 kVA maximum apparent power at the grid port. It has eight MPPTs, 200 kW maximum PV input and two battery inputs; use these figures when the grid application names the 99.99 model.
GoodWe GW99.99K-ET-G10

ET Series
99.99 kVA at the grid port
Eight MPPTs and two battery inputs are listed for this exact model.
Technical data
Power & Phase
- Phase
- 3
- Nominal power (kW)
- 99.99
- Max. apparent power to / from grid (kVA)
- 99.99
- Power factor
- 0.8 leading ~ 0.8 lagging
PV Input
- Max. input power (kW)
- 200
- Max. input voltage (V)
- 1000From 950 V to 1,000 V the inverter enters standby and returns to operation at 950 V.
- MPPT operating voltage range (V)
- 160 ~ 950
- Nominal input voltage (V)
- 620
- Max. MPPT current (A)
- 42 × 8
- Number of MPPTs
- 8
- Number of strings per MPPT
- 2
Battery Interface
- Battery type
- Li-Ion
- Nominal battery voltage (V)
- 600
- Battery voltage range (V)
- 300 ~ 800
- Number of battery inputs
- 2
Efficiency & Protection
- Max. efficiency
- 98.1%
- European efficiency
- 97.7%
- Max. battery to AC efficiency
- 98.2%
- MPPT efficiency
- 99.9%
- Ingress protection rating
- IP66
- Cooling method
- Smart fan cooling
Physical & Comms
- Dimension (W × H × D mm)
- 995 × 758 × 358
- Weight (kg)
- 97
- Operating temperature range (°C)
- -35 ~ +60
- Communication with BMS
- CAN
Project fit
Where this model fits.
Scenarios that show which projects the GoodWe GW99.99K-ET-G10 belongs in, and the limits behind our engineers' recommendation.
The 99.99 model in the grid application

The project documents call for this exact G10 nameplate rather than an adjacent 100 kW model.
The datasheet lists 99.99 kW nominal and 99.99 kVA maximum to and from the grid for this model.
- Application: under the exact name GW99.99K-ET-G10.
- Grid figure: 99.99 kVA.
Documents

Product questions
Which model figure should the grid application use for GW99.99K-ET-G10?
Use 99.99 kW as the model figure for the GW99.99K-ET-G10. The datasheet lists the model as GW99.99K-ET-G10, and the user manual gives the three-phase unbalanced output as 1/3 x 99.99 kW.
Compatibility records
GoodWe GW61.4-BAT-AC-G10Item number DLK-GOODWE-GW614BATACG10
GoodWe GW112.6-BAT-AC-G10Item number DLK-GOODWE-GW1126BATACG10
GoodWe GW208.9-BAT-LC-G10Item number DLK-GOODWE-GW2089BATLCG10Two GoodWe documents carry this pair: the Battery Compatibility Overview, ET (80–100 kW) column, and a signed Compatibility Statement of 2025-04-07 naming GW80K-ET-G10, GW99.99K-ET-G10 and GW100K-ET-G10 against GW61.4 to GW112.6-BAT-AC-G10.
Two GoodWe documents carry this pair: the Battery Compatibility Overview, ET (80–100 kW) column, and a signed Compatibility Statement of 2025-04-07 naming GW80K-ET-G10, GW99.99K-ET-G10 and GW100K-ET-G10 against GW61.4 to GW112.6-BAT-AC-G10. The Battery Compatibility Overview (p. 6) states that GW61.4-BAT-AC-G10 paired with ET (80–100 kW) cannot reach the inverter's full power output. GoodWe's BAT-C datasheet (p. 2) gives the GW61.4-BAT-AC-G10 an operating voltage range of 275.52 to 346.56 V (nominal 307.2 V); the ET 75–100 kW datasheet (p. 2) gives a battery voltage range of 300 to 800 V and a start-up voltage of 300 V.
GoodWe's Battery Compatibility Overview (p. 6) lists GW208.9-BAT-LC-G10 in its ET (80–100 kW) column.