Search the site

Description

SAJ HS2-5K-T2-X is the 5 kW three-phase hybrid inverter of the HS2 all-in-one system: 5000 W rated AC power, up to 7500 Wp of PV on two MPPT inputs, and a battery port for two to five BU2-5.0-HV1 modules.

Rated AC output
5 kW
Max PV input
7.5 kWp
MPPT
2
Battery voltage
180–600 V
Matched batteries
1

SAJ HS2-5K-T2-X (5 kW three-phase hybrid inverter)

  • 5000 W rated AC power and 5500 VA maximum apparent power on a three-phase 3L+N+PE connection.

  • Up to 7500 Wp of PV at STC on two MPPT inputs with a maximum DC input current of 16 A / 16 A.

  • Battery port for two to five BU2-5.0-HV1 modules: 180 to 600 V, 30 A maximum charging and discharging current.

  • Backup output of 5000 VA with 10000 VA peak apparent power for 60 s; with the UPS function the switch time is ≤ 10 ms.

5000 W rated AC power, 5500 VA maximum.

On 3L+N+PE the rated output current is 7.2 A at 230 V AC and the maximum output current 8.3 A. The power factor range is 0.8 leading to 0.8 lagging, and the total harmonic distortion of the current (THDi) is below 3 %. Maximum efficiency is 98.0 %, European efficiency 97.6 %.

Two to five BU2-5.0-HV1 modules at 30 A.

The battery port works from 180 to 600 V with a maximum charging and discharging current of 30 A. Two to five BU2-5.0-HV1 modules connect to one inverter, which gives 10.0 to 25.0 kWh nominal and 9.0 to 22.5 kWh usable energy. The battery modules are separate products with their own page.

IP65, natural convection, under 35 dBA.

The inverter measures 450 × 626 × 365 mm (H × W × D) and is cooled by natural convection. It operates from -10 to +50 °C with derating above 45 °C, and up to 4000 m altitude with power derating above 3000 m. Floor mounting and wall mounting are both possible, indoors or outdoors; 50 cm of clearance is kept above, in front and on both sides.

7500 Wp of PV on two MPPT inputs.

HS2

7500 Wp of PV on two MPPT inputs.

The PV side takes up to 7500 Wp at STC, a maximum DC voltage of 1000 V and an MPPT voltage range of 180 to 900 V; the start voltage is 180 V. The two MPPT inputs carry a maximum DC input current of 16 A / 16 A and a maximum DC short-circuit current of 19.2 A / 19.2 A. DC surge protection is integrated; AFCI and RSD protection are optional.

Technical data

Three-phase hybrid inverter of the HS2 all-in-one system.

Rated AC power
5000 W
Max. PV array power (STC)
7500 Wp
Max. charging / discharging current
30 A
Max. DC input current
16 A / 16 A
About these specifications

5000 W rated AC power with up to 7500 Wp of PV.

The HS2-5K-T2-X delivers 5000 W rated AC power and 5500 VA maximum apparent power. Two MPPT inputs take up to 7500 Wp, and the battery port charges and discharges two to five BU2-5.0-HV1 modules with up to 30 A.
PV input
Max. PV array power
7500 Wp
at STC
Max. DC voltage
1000 V
MPPT voltage range
180–900 V
Rated DC voltage
600 V
Start voltage
180 V
Max. DC input current
16 / 16 A
Max. DC short-circuit current
19.2 / 19.2 A
Number of MPPTs
2
Battery connection
Battery type
LiFePO4
Battery voltage range
180–600 V
Max. charging / discharging current
30 / 30 A
Battery modules
BU2-5.0-HV1, 2 to 5 modules
AC output (on-grid)
Rated AC power
5000 W
Max. apparent power
5500 VA
Rated output current
7.2 A
at 230 V AC
Max. output current
8.3 A
Inrush current
52.0 A
Max. AC fault current
45.0 A
Max. AC overcurrent protection
20.8 A
Rated AC voltage
3L+N+PE, 220/380 V, 230/400 V
AC voltage range
180–280 / 312–485 V
Rated output frequency / range
50, 60 / 45–55, 55–65 Hz
Power factor (cos φ)
0.8 leading – 0.8 lagging
Total harmonic distortion (THDi)
< 3 %
AC input (on-grid)
Rated AC voltage
3L+N+PE, 220/380 V, 230/400 V
AC voltage range
180–280 / 312–485 V
Rated input frequency
50, 60 Hz
Max. input current
14.5 A
at 230 V AC
AC output (backup)
Max. output power
5000 VA
Max. output current
8.0 A
Peak output apparent power
10000 VA
for 60 s
Rated AC voltage
3L+N+PE, 220/380 V, 230/400 V
AC voltage range
180–280 / 312–485 V
Rated output frequency / range
50, 60 / 45–55, 55–65 Hz
Output voltage distortion (THDv)
< 3 %
at linear load
Switch time
≤ 10 ms
with UPS function
Efficiency
Max. efficiency
98.0 %
European efficiency
97.6 %
Protection
Battery input reverse polarity protection
Integrated
Overload protection
Integrated
AC short-circuit current protection
Integrated
DC surge protection
Integrated
AC surge protection
Integrated
Anti-islanding protection
Integrated
AFCI protection
Optional
RSD protection
Optional
Interfaces
PV connection
MC4 / D4
AC connection
Plug-in connector
Battery connection
Quick connector
Display
LED + app
Communication
Wi-Fi / Ethernet / 4G (optional)
General data
Topology
Non-isolated
Operating temperature range
-10 to +50 °C
derating above 45 °C
Cooling
Natural convection
Ambient humidity
0–100 %, non-condensing
Max. altitude
4000 m
power derating above 3000 m
Noise
< 35 dBA
Ingress protection
IP65
Dimensions (H × W × D)
450 × 626 × 365 mm
Warranty (years)
10
Standards
EN 62109-1/2, EN 61000-6-2/4, EN 50438, EN 50549, C10/11, IEC 62116, IEC 61727, RD 1699, RD 413, UNE 206006, UNE 206007, NTS, CEI 0-16, AS 4777.2, NBR 16149, NBR 16150, VDE-AR-N 4105, VDE 0126-1-1

Documents

Product questions

Which battery modules does the HS2-5K-T2-X take, and how many?

The HS2-5K-T2-X uses BU2-5.0-HV1/5 battery modules (1P32S, 102.4 V, 50 Ah). The number of modules ranges from 2 to 5.

What does the backup output of the HS2-5K-T2-X deliver when the grid fails?

The backup output of the HS2-5K-T2-X delivers a maximum output power of 5000 VA and a maximum output current of 8.0 A. The peak output apparent power is 10000 VA for 60 s.

What does the AC side of the HS2-5K-T2-X need at installation?

For safety and compliance, install a 63 A air circuit breaker or higher between the grid and the inverter. Do not connect multiple inverters to one AC circuit breaker in parallel operation.

Compatibility records

Compatible modelCategoryRatingStatus & required accessory
SAJ BU2-5.0-HV1Item number DLK-SAJ-BU250HV1Home Storage5 kWhReleased [1] [2] [3]
  1. The HS2 takes two to five BU2-5.0 battery modules (HS2/AS2 manual V0.3, PDF p12). Battery voltage range 180 to 600 V.
  2. One BU2-5.0 module alone operates at 89.6 to 115.2 V (SAJ's B2 datasheet gives this for the one-module B2-5.0), below the HS2's battery voltage range of 180 to 600 V; the HS2 manual gives two modules as the smallest stack.
  3. The HS2 takes two to five BU2-5.0 battery modules (HS2/AS2 manual V0.3, PDF p12). Battery voltage range 180 to 600 V. One BU2-5.0 module alone operates at 89.6 to 115.2 V (SAJ's B2 datasheet gives this for the one-module B2-5.0), below the HS2's battery voltage range of 180 to 600 V; the HS2 manual gives two modules as the smallest stack.
View full inverter & battery compatibility matrix

Compare models in this series

ModelRated AC outputMax PV inputPhasesMPPTBattery voltageProtectionMatched batteries
HS2-5K-T2-X5 kW7.5 kWp32180–600 VIP651
HS2-6K-T2-X6 kW9 kWp32180–600 VIP651
HS2-8K-T2-X8 kW12 kWp32180–600 VIP651
HS2-10K-T2-X10 kW15 kWp32180–600 VIP651