Search the site

Description

Three-phase 120 kW commercial string inverter (132 kW / 132 kVA max AC output, 1,100 V max DC input, 12 MPPTs with 30 A per MPPT, IP66) for large rooftop and ground-mounted PV plants. Supports 3L/N/PE and 3L/PE grid connections (TN-S, TN-C, TN-C-S, TT, IT) and holds a VDE-AR-N 4110 unit certificate.

The third image shows the optional LCD version.

Rated AC output
120 kW
Max PV input
180 kWp
MPPT
12
Grid standard
EN 50549
Phases
3

GoodWe GW120K-HT

Technical data

PV input
Maximum PV input power
180000 W
Printed as Max. Input Power: 180 kW in the HT 100–136K User Manual (p. 53).
Maximum input voltage
1100 V
Nominal input voltage
600 V
Start voltage
200 V
MPPT voltage range
180 ~ 1000 V
MPPT voltage range at rated output
500 ~ 850 V
Number of MPPTs
12
Strings per MPPT
2
Maximum input current per MPPT
30 A
Maximum short-circuit current per MPPT
45 A
PV standby voltage range
1000 ~ 1100 V
Between 1,000 V and 1,100 V the inverter enters waiting mode and resumes normal operation when PV voltage returns to 180–1,000 V.
AC output
Rated active power
120 kW
Maximum active power
132 kW
Rated apparent power
120 kVA
Maximum apparent power
132 kVA
Rated output current
173.2 A
Maximum output current
191.3 A
Grid connection
3L / N / PE or 3L / PE
Maximum efficiency
98.6 %
European efficiency
98.3 %
Installation and operation
Dimensions (W × H × D)
1008 × 678 × 343 mm
Weight
98.5 kg
Ingress protection rating
IP66
Operating temperature
-30 ~ +60 °C
Full load operation up to 45 °C (EMEA Datasheet, p. 1).
Maximum operating altitude
5000 m
Derating above 4,000 m.
Cooling
Smart Fan Cooling
Communication interfaces
RS485, WiFi or 4G (Optional); Modbus-RTU (SunSpec Compliant)
Night-time power consumption
<2 W

Documents

Product questions

Which grid earthing systems and AC wiring modes does the GW120K-HT support?

The GW120K-HT supports TN-S, TN-C, TN-C-S, TT and IT grids at 400 V. The manual shows connections with and without neutral (3L/N/PE or 3L/PE). On TT grids the neutral-to-earth voltage must be below 20 V RMS. Each inverter needs its own AC circuit breaker. GoodWe recommends 250 A and, if local rules call for an external RCD, a Type A device rated at 1,200 mA or higher (manual, PDF pp. 10 and 28).

What happens if PV string open-circuit voltage on the GW120K-HT exceeds 1,000 V?

Per the user manual (pp. 25 and 53), open-circuit voltage on each MPPT must never exceed 1,100 V. When PV input voltage is between 1,000 V and 1,100 V, the GW120K-HT enters waiting mode and automatically resumes normal operation once the input voltage returns to the 180–1,000 V MPPT operating range (500–850 V MPPT range at nominal power; maximum DC input power 180 kW).

Which grid-connection documents cover the GW120K-HT?

The GW120K-HT holds a German medium-voltage VDE-AR-N 4110 unit certificate (SGS CEBEC Unit Certificate No. 2621/0136-CER, software version 04.04.04, p. 1), an NC RfG equipment certificate covering Poland’s PTPiREE/PSE implementation for types A–D (DNV Certificate No. TC-GCC-DNVGL-SE-0124-07790-1, p. 1), and an EN 50549-1 certificate.

How is grid export power limitation and plant monitoring configured on the GW120K-HT?

For a plant with several GW120K-HT inverters, the GoodWe manual shows the SEC1000 controlling export via RS485 on COM2. It separately shows the EzLogger Pro and EzLogger3000C for monitoring. For a single inverter, the optional COM4 port connects the meter for export control. The manual shows the GM3000C, and the HT 1100 V compatibility list also includes the GM330 (IoT compatibility list V18, PDF p. 7).

Can the GW120K-HT connect directly to a battery cabinet?

The GW120K-HT is a grid-tied PV string inverter. Its DC inputs accept PV strings. There is no battery connection. A storage installation needs a separate battery inverter or a hybrid inverter with a compatible battery port.

What European manufacturer warranty applies to the GW120K-HT?

GoodWe’s European inverter warranty gives the GW120K-HT five years of cover. The period starts at first installation or twelve months after production, whichever is earlier. If the installation date cannot be documented, GoodWe uses its shipment date in place of the installation date.

Check system compatibility

Check which equipment works with GW120K-HT in your project.

Compare models in this series

ModelRated AC outputMax PV inputPhasesMPPTProtectionGrid standard
GW100K-HT100 kW150 kWp310IP66EN 50549
GW120K-HT120 kW180 kWp312IP66EN 50549

Planning & Commissioning Guides