DEHN DG YPV SCI 1000 (type 2 DC surge arrester, 1000 V PV)

Type 2 DC surge arrester for the PV side of a string inverter, up to 1000 V.

  • Type 2 to EN 50539-11, 1000 V DC max PV voltage, 12.5 kA nominal and 25 kA max discharge
  • Three-step d.c. switching device: disconnects and short-circuits, then isolates - a 1000 V DC arc is extinguished immediately instead of being held
  • Green/red flag per protective circuit, so a spent path is visible without a meter
  • Specified for string-inverter systems to 1000 A short-circuit current, per IEC 60364-7-712
Manufacturer
DEHN
Model code
DG YPV SCI 1000
Item no.
DLK-DEHN-DGYPVSCI1000
Delivery
Delivery to Germany · EUR 14.90 at checkout
Orderable · lead time confirmed after order

Plan with DG YPV SCI 1000

New system, extension or replacement? Linker Advisor starts from this article and asks only for what is still open — existing model, quantity, postcode, installation date.

Figures transcribed from the manufacturer datasheet on file. Confirm your grid code and configuration with our engineers before ordering.

  • GoodWe · SAJ · Pylontech · EcoFlow · Chint paired from the maker’s own lists
  • Datasheets on file for every item
  • Within 24 h engineering response
  • MOQ 1 unit Â· EU delivery
  • Engineering-checked configurations
Documentation

Specifications

Every value exactly as published in the official DG YPV SCI 1000 documentation.

SPD typeType 2 according to EN 50539-11
Max. PV voltage (UCPV)1000 V
Short-circuit current rating (ISCPV)1000 A
Nominal discharge current In (8/20 µs, DC± → PE)12.5 kA
Max. discharge current Imax (8/20 µs)25 kA
Voltage protection level (UP)≤ 4 kV
ConfigurationMultipole, fault-resistant Y circuit of three protective paths
DisconnectionThree-step d.c. switching device (patented SCI principle)
Status indicationGreen / red indicator flag per protective circuit
Remote signallingNone on this part numberthe FM version 950 535 adds a floating changeover contact
Supply formPrewired complete unit
PV systemsAll PV systems according to IEC 60364-7-712
Designed forString inverter systems with system current up to 1000 A
Tested toEN 50539-11
ApprovalsKEMA, UL
Manufacturer part number950 530
EAN4013364152960
Weight300 g
Ask an engineer

Configuration 1

No. This is part number 950 530, which has the green/red indicator flags on the front but no signalling terminal.

If your monitoring needs a dry contact, the part you want is 950 535 (DG YPV SCI 1000 FM), which adds a three-pole floating changeover contact. Ask and we will quote it.

Compatibility 1

No. UCPV is 1000 V, which covers the string inverters we sell — their PV inputs are rated 1000 V. A 1500 V array needs a 1500 V arrester; DEHN makes them (the ME YPV SCI 1500 family) and we can source one.

Installation 1

On the DC side between the array and the inverter, as close to the inverter as the wiring allows, in the combiner or the inverter's own DC compartment. It is a prewired complete unit, so it is a mount-and-connect job, not an assembly.

Protection level UP ≤ 4 kV is what has to sit under your inverter's DC surge withstand — check that figure on the inverter datasheet, not on this page.

Ordering 1

German catalogues list the modular DEHNguard M YPV SCI 1000 (part 952 510) far more prominently than this compact one, and it is easy for a supplier to send it instead. It is a different device.

Its short-circuit current rating is 10 kA. This one is 1000 A. They are not interchangeable, and the compact is the part specified for string inverter systems up to 1000 A. If a delivery arrives as 952 510, it is the wrong item — send it back.

Product information 2

Both. Used in both residential and commercial work. It is filed under one segment because the shop keeps one category per accessory; the part itself is not segment-specific.

Because we do not have one of this part, and we will not show you a different manufacturer's part in its place. Everything on this page is read from the manufacturer's own datasheet, which is linked above.

Ask us and we will send the manufacturer's product images with the quote.

Next step

Send the project. Hear from an engineer within 24 hours.

Loads, tariff, site constraints - our engineers reply with a compatibility check and a sizing recommendation.

Contact project support

Or write to linker01@de-linker.com — attach your load profile if you have one.